PK4514

PK4514

PK4514 complete Power Quality Analysis System includes PS4550 Power Quality Analyzer, four HA1000 clamp-on current probes, and our CAS3 hard-shell carrying case. 

The PK4514 is the ideal package for comprehensive power quality studies, energy audits, load studies, harmonic analysis, and more.  Wide-range highly-accurate clamp-on current probes allow you to get the most accurate answers for AC power measurements.
Advanced PowerSight Manager software improves your efficiency and eliminates sources of error at each stage of the monitoring process.  CAT IV safety rating and wireless remote control via Bluetooth for even greater safety.  SD memory card for redundant storage and essentially unlimited logging capacity.

PURCHASE or RENT:  We are the largest power analysis rental service in the USA.  You are renting from the manufacturer for the best technical support and fast delivery.  Rent or buy from 1 to 100 systems at a time.

$6,370 USD (purchase price)

Add to cart

($750 per month rental, $575 for 2 week rental, $425 for 1 week rental)

PK4514 complete Power Quality Analysis System includes PS4550 Power Quality Analyzer, four HA1000 clamp-on current probes, and our CAS3 hard-shell carrying case.  The PK4514 is the highest accuracy package for comprehensive power quality studies, energy audits, load studies, harmonic analysis, and more.

Features

Measure and log all common power measurement types:  V, A, W, VA, VAR, kWH, PF, Hz, THD, etc.

Capture power quality events in multiple ways to view and record swells, dips (sags), inrush, high speed transients, etc of both voltage and current.  All inputs are sampled continuously and simultaneously so nothing is missed.

Wide range of fundamental frequency modes for 50Hz, 60Hz, 400Hz, variable frequency systems, and DC to cover all your needs.

Able to evaluate all power systems: 3 phase Wye, 3 phase Delta (including 4-wire, open, and grounded), split-phase, single phase, quad single phase (using same source) , 3PT/3CT, 3PT/2CT, 2 current power, DC, quad DC (using same source).

The included Advanced PowerSight Manager software (PSM-A) improves your efficiency and eliminates sources of error at each stage of the monitoring process:

  • TestPlan Manager™ to organize and automate your tests and the data retrieval
  • SureStart™ expert system to advise if the connections or settings seem correct or not, prior to starting
  • DataSetup Wizard™ to set your triggering and logging parameters according to your application
  • ReportWriter Wizard™ to automatically generate error-free reports.

Benefit from the safety rating of 1000V CAT IIII, 600V CAT IV and Bluetooth Wireless Communications (remote viewing/control of the display without the burden of wearing PPE).

SD Memory for redundant storage and essentially unlimited logging capacity.

Extend the measurement range with the use of our industry-widest array of accessories and options:

  • measure from 0.002 to 6,000 amps AC (HA-GFD/eFX6000)
  • measure from 5 to 2000 amps DC (DC600/DC2000)
  • direct connect and measure to 15kV (5KVP/15KVP)
  • measure power-line noise to 100kHz (FAO)

Comes with 4 HA1000 clamp on current probes. These are a highly recommended choice for high-accuracy current measurement. The range is from 1A to 1,000A AC and their superb sensitivity is what makes them so precise. The HA1000’s wide measurement range and precision means it is suitable for most power monitoring studies. For a more versatile option, our eFX6000 probes come standard with our higher-tier system, the PK4564.

 

First rate technical support, direct from the manufacturer to you!

Specifications

General Specs

Category Notes
Size PS4550 Analyzer:  3.88″ (9.86 cm) W x 7.72″ (19.61 cm) L x 1.58″ (4.01 cm) Deep at bottom end; 2.14″ (5.44 cm) Deep at top end
Weight PS4550 Analyzer:  1.1 lbs (0.5 kg)
Operating Range 32 – 122 degrees F (0 – 50 degrees C) Relative humidity to 70% (non-condensing)
Power Requirement 12V DC @ 500 mA
Battery Life 8-10 hours after 4 hour charge
Battery Type Li-ion
Sampling Rate 8 microseconds for Voltage and Current, continuous/simultaneous
Safety 600V CAT IV, 1000V CAT III
SD Card Slot Accepts SD Cards to 32GB (SDHC)
Logging Period (Resolution) 1 Second – 99 Minutes, set by user
Logging Duration (Length of session) up to 2 years according, depending on memory allocation
Internal Data Retention 8 years
Other Features Crest Factor, K Factor, Peak Demand Period, Peak Demand of Peak, Demand Period, Duty Cycle, On/Off Cycle %, Avg. On Time, Avg Off Time

Voltage Measurement

Category Notes
Direct Measurement Range 1 – 1000V (15,000V using optional 15KVP)
Measurement Range 1V – 6 megavolts (using input ratios and PTs)
Accuracy ±0.1% of reading ±0.3 V to 400V, ±3V to 1000V

Current Measurement

Category Notes
Direct Measurement Range 1.0A – 1000A (0.002 – 6,000A using HA-GFD/eFX6000)
Measurement Range 0.001A – 6 megamps (using input ratios and CTs)
Accuracy ±0.5 % of reading, including accuracy of probes

Power Measurement

Category Notes
Direct Measurement Range 1 – 3 megawatts (assuming 1000V, 1000A, PF=1.00, 3-phase power)
Display Range from 0.002W (using optional HA-GFD) to 999 megamps (using input ratios and CTs)
Accuracy ±0.5 % of reading, including accuracy of probes